Terreon® 54" Circular Deep Bowl Washfountain with Air Metering Valve
TDB3108, WF3208 Installation Instructions
Bradley Corporation • 215-1471 Rev. E; EN 06-915B18 4/6/2007
Installation Instructions continued . . .
NOTE: The Vernatherm TMA valve is NOT factory preset. Upon installation, the temperature of
this valve must be checked and adjusted to ensure delivery of a safe water temperature. Water in
excess of 110°F (43°C) may cause scalding.
4. Check the temperature when approximately 1.0 GPM water flow is reached and adjust if neces-
sary (the range of the valve is 95°F–115°F (35°C–43°C). To adjust the temperature, follow the
procedure below:
• Loosen temperature locking nut with wrench.
Using a blade screwdriver, turn the adjustment stem counterclockwise to increase the tempera-
ture or clockwise to decrease the temperature (Figure 12).
• Once desired temperature is reached, tighten nut to prevent temperature change.
5. Clean sprayhead if necessary. See page 25 for sprayhead maintenance and repair parts. Adjust the
volume control valve, if necessary, to control the flow of water.
6. Attach pedestal access panel with hardware provided.
7. Attach kick plate to pedestal base with hardware provided.
TEMPERATURE
ADJUSTMENT
STEM
TEMPERATURE
LOCKING
NUT
Figure 12