Bradley S19-921 Installation Guide Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
6
S19-921 Installation
7/29/2014 Bradley • 215-1546 Rev. N; ECN 14-05-017
Maintenance
Follow the manufacturer’s instructions for the proper use of water preservative.
Inspect eyewash unit
1. Visually inspect the eyewash unit weekly for cleanliness and proper solution level (per ANSI Standard
Z358.1-2009).
2. Activate the eyewash unit each time the solution is replaced to ensure proper operation. If the unit is not
working properly, remove it from the hazard area and contact Bradley Corporation immediately.
Check the sprayheads’ water spray pattern for an even, continuous flow. The sprayheads are attached
to the arm with screws and can be detached from the tray for cleaning or obstruction removal, if
necessary, and reattached (use a ⁹⁄₆₄" hex-head Allen wrench to remove and reinstall the sprayheads).
Check the water supply hose at the basin of the eyewash unit for cracks, leaks or wear.
Check the entire unit for possible water leakage.
Check the solution for contamination and replace with fresh solution, if necessary.
Clean eyewash unit
When using potable water and water preservative (recommended):
1. Carefully remove the eyewash tank from the pedestal and drain the water solution from the tank (dispose
of the solution properly). For ease of draining, the pedestal has a drain hole which will accept a ½” I.D.
tube at the underside of the hole (tube supplied by others) (see page 5 for drain hole location).
2. Clean the inside of the tank using warm water and a mild soap product; rinse thoroughly.
3. Refill the eyewash tank following the procedures outlined in Step 2 found on page 4. Follow instructions
of the preservative manufacturer for the proper use of water preservative.
4. Reinstall the eyewash tank following the procedure outlined in Step 2 found on page 4.
When using potable water only:
1. Empty the tank any time from once per week to once per month, depending on the quality of your water
supply. The manufacturer is not responsible for variations in the water supply.
2. Clean the inside of the tank using warm water and mild soap. Rinse the tank thoroughly with warm water.
3. Refill the eyewash tank with tepid potable water.
To operate eyewash unit
1. Begin operation by pulling down the tray.
2. Hold eyelids open with thumbs and forefingers. Rotate eyes back and forth to ensure a complete rinse.
Allow water to bathe both eyes simultaneously for a minimum of 15 minutes.
3. Seek medical attention immediately after use.
Do not lean on the eyewash tray when in the opened position. Damage
to unit may result.
Page view 5